Aquatherm Heat Pumps

AT160R

AT160R Technical Specifications
Performance Statistics
Water Temp / Ambient Air / Relative Humidity BTUs (British Thermal Units) Coefficient of Performance
80/80/80 128,000 5.7
80/80/63 120,000 5.5
80/50/63 78,000 4.0
Unit Specifications
Refrigerant R410A
Compressor Scroll
Heat Exchanger ThermoLink - Tube In Shell
Electrical Specifications
kW Input 6.7 kW
Voltage/Hz/Phase A: 208-230V/60hz/1 B: 208-230V/60hz/3
Min Circuit Ampacity A: 43.3
Max Fuse Size A: 60 B: 50
Water Flow
Max Flow (GPM) 30/70 GPM
Unit Dimensions
Installed Shipping
Weight (lbs) 273 lbs 313 lbs
Length x Width x Height (inches) 34"x34"x44" 37"x36"x51"
Technical Specifications Comparison
Model AT140R AT160R AT200R
BTUs (Water Temp/Ambient Air/Relative Humidity)
80/80/80 114,000 128,000 138,000
80/80/63 106,000 120,000 130,000
80/50/63 72,000 78,000 88,000
Coefficient of Performance (Water Temp/Ambient Air/Relative Humidity)
80/80/80 5.7 5.7 6.1
80/80/63 5.5 5.5 5.8
80/50/63 4.0 4.0 4.2
Unit Specifications
Refrigerant R410A R410A R410A
Compressor Scroll Scroll Scroll
Heat Exchanger ThermoLink – Tube In Shell ThermoLink – Tube In Shell ThermoLink – Tube In Shell
Electrical Specifications
kW Input 5.9 kW 6.7 kW 6.6 kW
Voltage/Hz/Phase A: 208-230V/60hz/1 A: 208-230V/60hz/1 A: 208-230V/60hz/1
B: 208-230V/60hz/3 B: 208-230V/60hz/3 B: 208-230V/60hz/3
Min Circuit Ampacity A: 38.5 A: 43.3 A: 42.1
B: 31.0 B: 33.3
Max Fuse Size A: 60 A: 60 A: 60
B: 50 B: 50 B: 50
Water Flow
Max Flow (GPM) 30/70 GPM 30/70 GPM 30/70 GPM
Weight (lbs)
Installed 264 lbs 264 lbs 264 lbs
Shipping 304 lbs 304 lbs 304 lbs
Length x Width x Height (inches)
Installed 34″x34″x44″ 34″x34″x44″ 34″x34″x44″
Shipping 37″x36″x51″ 37″x36″x51″ 37″x36″x51″